Connecting ABB PRO-33 Inverters

 PLEASE OBSERVE ALL MANUFACTURER SAFETY AND OPERATION INSTRUCTIONS

 

1. Ensure you have read a copy of the manufacturer operating and safety manual.  The latest copy  may be obtained from the manufacturer website ABB Document Library (website)

Please review document “Product manual PRO-33.0-TL string inverters” which can also be found here. If you are using a different inverter type, then obtain the correct Operating Manual or contact Ardexa.

 

2. Refer to “Product manual PRO-33.0-TL string inverters” page 64. If you are using a different inverter type, then obtain the correct Operating Manual or contact Ardexa.

 

3. Connect each inverter using D+/D-/GND RS485 as per the installation manual. Then connect the RS485 line to the local device. When connecting to the local device; connect the “D+” cable to the “485 +” and the “D-” to the “485 -” and “GND” to ground. Just 3 wires.

 

4. Terminate the last PRO-33 inverter in the chain by switching switch S1:2 (Terminating Resistor) inside the inverter to ON. The switch is located on the communication board and should be marked “S1”.

Note well: Some versions of the ABB documentation are incorrect. You DO NOT need a termination resistor (it makes no difference) at the "local device end". And you MUST switch the last inverter S1:2 switch to ON. If in doubt, turn on both S1 switches to ON.

 

5. Set the RS485 address in the inverter (see inverter documentation). But make sure all inverters are set to RS485 unique addresses.

 

6. If Ardexa is completing your plugin configuration, please don't forget to send:

a. Clear photographs of both ends of the RS485 cable termination (to the first inverter)

c. The number and models of connected inverters

d. The unique RS485 or IP addresses of the inverters

e. The name of the site.

 

 

 